MSU 4.0
Manual Start Units - MSU Series

Provides flexible start and control functions for Diesel Generators...

MSU4.0 control panel offers extensive start and control functions for Gen-Sets, where mains control is not required.

  MSU4.0 Automatic/Manual Start control unit is designed for single Generators, where mains line monitoring is not required. The unit has all the necessary functions to start the Diesel engine safely and control engine parameters, while monitoring the alternator voltage and load current. All voltage and current values are monitored in True RMS values and displayed on the panel. There is no need for additional panel meters. Load power is also measured and ... »

 

MSU4.0 Automatic/Manual Start control unit is designed for single Generators, where mains line monitoring is not required. The unit has all the necessary functions to start the Diesel engine safely and control engine parameters, while monitoring the alternator voltage and load current.

All voltage and current values are monitored in True RMS values and displayed on the panel. There is no need for additional panel meters. Load power is also measured and displayed. User can operate functions on these values.

The unit also provides all the necessary protection and monitoring of the engine values. The engine temperature and oil pressure is also displayed on analog bar graph displays, hence eliminating the use of additional gauges on the panel. Pre-heat function can be used for secure starting under very cold whether conditions. 

The DC battery voltage is measured and displayed. Alarm function can also be initiated, depending on the battery supply voltage. All alarms are logged and the last 10 alarms can be seen in the past log records. The unit can be remotely controlled by a remote start input function, hence allowing gen-set to be controlled by other systems. Engine working hours are recorded in the system memory. Load power is also measured and monitored and special functions can be activated on these measured values. User can also program periodic service time for the engine.

The unit has configurable i/o ports which can be programmed according to user application. Analog measuring input calibration can be made from the menu. There is no need to open the unit enclosure. Five digital displays allow most critical values to be displayed simultaneously, which allows easy monitoring from the front panel.

«

↑ Top KEY FEATURES
↑ Top KEY BENEFITS

 

DC Supply (Power Supply)
 

  • DC Supply Voltage :
    9 - 35 Vdc
     
  • Maximum Operating Current :
    For 12V Systems    mA
    For 24V Systems    mA
     
  • Stand-by Operating Current :
    For 12V Systems     mA
    For 24V Systems     mA
     
  • Cranking Dropouts :
    Able to withstand dopouts during cranking
     

 

Instrumentation

 

  • Digital Display Type :
    5 Displays with 3 x 7 Segment LED's
    2 Analog Bar-Graph Displays for Analog Inputs 

     
  • Information Shown on Digital Display :
    Generator Voltage and Frequency (Phase-Phase and Phase-Neutral)
    Current, RPM, Battery Voltage
    Coolant Temperature, Oil Pressure
    Engine Running Hours

     
  • Alarm & Event Log :
    Last 10 Alarms are Logged
     
  • LED Indicators :
    Mimic Diagram
    8 Failure and Mode LED Indicators
     

Generator and Mains Voltage / Frequency Measurement
 

  • Measurement Type and Source :
    True RMS 3 Generator Voltage Inputs
     
  • Phase-Neutral Voltage Measurement Range :
    20 - 300 Vac
     
  • Phase-Phase Voltage Measurement Range :
                   Vac
     
  • Voltage Measurement Accuracy :
    +/- 2% of the Scale
     
  • Voltaj Measurement Resolution:
    1.0 V
     
  • Frequency Measurement Range:
    1-99Hz
     
  • Frequency Measurement Accuracy :
    +/- 0.1Hz
     
  • Frequency Measurement Resolution :
    0.1 Hz

 

Current Measurement

 

  • Measurement Type : 
    3 Phase True RMS
     
  • Current Transformer Seconder Ratio :
    The Primer and Seconder Ratios are x/5A
     
  • Measurement Accuracy :
    +/- 2%
     
  • Measurement Resolution :
    1.0 A
     

Digital Inputs
 

  • Digital Inputs  :
    4 Digital Inputs
     
  • Configurable Inputs :
    4 Configurable Inputs
     
  • Operation Type :
    The Inputs are Activated via Negative Battery Terminal
     

Analog Inputs

 

  • Analog Oil Pressure Measurement Type :
    Resistive
     
  • Analog Oil Pressure Measurement Accuracy :
    +/- 1%
     
  • Analog Oil Pressure Measurement Resolution :
    0.1 Bar
     
  • Analog Coolant Temperature Measurement Type :
    Resistive
     
  • Analog Coolant Temperature Measurement Accuracy :
    +/- 1%
     
  • Analog Coolant Temperature Measurement Resolution :
    0.1 ºC
     
  • Analog Fuel Level Measurement Not Supported in this Model
Charge Failure Input

 

  • Voltaj Range :
    0 - 35 V
     
  • Excitation Current :
    For 12V Systems 80mA
    For 24V Systems 160mA
     
  • Measurement Accuracy : 
    Not Supported in this Model
     
  • Measurement Resolution :
    Not Supported in this Model
     

Magnetic Pick-up Input (MPU, RPM)

 

  • Not Supported in this Model

     

Outputs
 

  • Mains and Generator Contactors :
    2 Outputs 10A 250Vac Relay
     
  • Crank and Fuel :
    2 Outputs 6A 250Vac Relay
     
  • Configurable Aux. Outputs :
    2 Outputs 6A 250Vac Relay
     

Communication

 

  • Not Supported in this Model

 

Real-time Clock
 

  • Not Supported in this Model

     

Environmental Conditions

 

  • Operating Temperature and Humidity Range :
    -35ºC to +70ºC
    20%rH to 99%rH, Non-condensing
     
  • Storage Temperature and Humidity Range :

     
  • ESD Protection :

     
  • EMC Conformance :

     
  • EMI Conformance :

     
  • Vibration :

     
  • Protection Class :
    IP 52 Front Panel Protection

 

Mechanical Specifications

 

  • Dimensions 
    192 mm x 144 mm x 62 mm
     
  • Panel Cut-out :
    185 mm x 138 mm
     
  • Weight : 
    770 gr (Average)
     
  • Mounting Type :
    Panel Mount with Metal Screw Fixings
    Maximum Panel Thickness 3mm
     